EXPANSION VALVE (FOR COOLING) INSPECTION
1. Disconnect the expansion valve (for cooling) connector.
2. Measure the resistance value between the terminals of the expansion valve (for cooling) side connector.
If it is out of standard value, replace the expansion valve (for cooling).
TerminalStandard value
258.0 – 10.0 Ω (At 20°C (68°F))
148.0 – 10.0 Ω (At 20°C (68°F))
21No continuity