SIMPLE INSPECTION OF THE REFRIGERANT PRESSURE SENSOR
1. Assemble a gauge manifold on the high pressure service valve.
2. Disconnect the refrigerant pressure sensor connector and connect the special tool test harness (MB991658) as shown.
3. While the READY (ready to drive) indicator illuminates, turn on the air conditioner switch.
4. At this time, check to see that the voltage of the refrigerant pressure sensor connector terminal No. 2 reflects the specifications of the figure.
noteThe allowance shall be defined as ±5%.